952 research outputs found
Guidelines for Measuring Air Infiltration Heat Exchange Effectiveness (IHEE), Submitted to the Texas Higher Education Coordination Board Energy Research Application Program Project #227
This report presents three methods of measuring the air infiltration heat recovery in
buildings. The blower door method estimates the air infiltration heat recovery using a test
which takes less than one hour, and gives information to the contractors making retrofit
decisions. The co-heating method identifies the relationship between the infiltration heat
recovery and the air flow rate using two or three nights of testing. This method has higher
accuracy than the blower door method and is suitable for use by both contractors and
researchers. Finally, the STAM (short term average method) investigates the relationship
between air infiltration heat recovery and air flow rate, air flow direction, and solar
radiation. This is a comprehensive method which is most suitable for use by researchers.This report is presented to the Texas Higher Education Coordination Board as a
deliverable under the Energy Research and Applications Program Project #227, which
targeted reducing the design size of HVAC systems in houses since the actual air
infiltration energy consumption is less than the design values due to air infiltration heat
recovery in house components
The Measured Energy Impact of Infiltration in an Outdoor Test Cell
The energy consumption calculation of house envelopes assumes that conduction heat loss is independent on air infiltration heat loss, and that energy consumption is the sum of these losses. Anderlind [1985], Liu [1987], and Claridge et at. [1989] showed this method can overestimate energy consumption substantially under steady-state conditions. Bailly [1987] and Anderson [1987] reported much smaller house energy consumption when the air flow was organized by mechanical systems. However, none of these studies quantified energy loss reduction under a variety of outdoor weather conditions. The energy performance was investigated in an outdoor test cell with different leakage configurations and air flow rates under both infiltration and exfiltration. It was found that the energy consumption was not only dependent on air flow rate, temperature differences, and solar radiation, but also on the air flow direction and the air leakage configuration. Infiltration could lead to a much lower heating energy consumption than that of exfiltration, and exfiltration could lead to a much lower cooling energy consumption than that of infiltration. The air infiltration energy consumption of a leaky house could be 9 times as high as that of a tight house even when the air flow rate was the same for both houses
The Measured Energy Impact of Infiltration Under Dynamic Conditions
Energy consumption due to air infiltration is customarily assumed to equal the mass flow rate times the specific enthalpy difference between the inside and outside air. Anderlind showed theoretically that this represents an upper limit for the energy impact of infiltration with an idealized steady-state wall model. Claridge and Bhattacharyya found it to be 20% to 80% of the value customarily used in an indoor test cell and a frame wall under steady-state condition. However, in real buildings, the heat transfer process is a complicated non-linear process, and neither the temperature nor the air flow rate is constant. Therefore, the validity of the steady-state methodology should be proved for dynamic condition. As a preliminary step, dynamic tests were conducted by varying an indoor test cell temperature in a periodic manner for a variety of leakage configurations and air flow rates. The measurement results demonstrated that the cell envelope can be treated as a linear system, and the steady-state methodology or time-averaging technique can be used for the treatment of energy performance when a constant air flow rate is present
An Advanced Economizer Controller for Dual Duct Air Handling Systems - with a Case Application
Heating penalty is expected when economizers
are applied to dual-duct air handling systems.
The heating penalty can even be higher than the
cooling savings when the hot air flow is higher
than the cold air flow. To avoid the excessive
heating penalty, advanced economizers are
developed in this paper. The application of the
advanced economizer has resulted in $7,00O/yr
savings in one 95,000 ft2 school building since
1993. The impacts of cold and hot deck settings
on the energy consumption are also discussed
Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation
Optimal hot and cold deck reset schedules
can decrease simultaneous heating and cooling
in VAV AHUs comparing with constant cold
deck temperature operation. In this paper,
optimization models are developed. The energy
impacts are simulated for a typical office
building in the hot and humid climate
(Galveston, Texas).
The simulation results show that the
optimized reset schedules can reduce the cost of
AHU energy consumption (cooling, heating and
fan power) by 8% to 20% in normal VAV
systems when the minimum air flow rate
increased from 30% to 70% of the maximum
flow
Potential Operation and Maintenance (O&M) Savings in the John Sealy North Building at UTMB
The LoanSTAR Monitoring and Analysis Group, Energy Systems Laboratory at Texas A&M University, was requested by University of Texas Medical Branch at Galveston to investigate O&M measures in their five LoanSTAR program buildings. This report describes the suggested O&Ms in John Sealy North Building, a surgical building of 54,494 ft2,which currently spends 502,100 per year on electricity, steam and chilled water. The suggested O&Ms include optimizing the outside air treatment cold deck reset schedule, the cold deck reset schedule and the hot deck reset schedule. These optimized HVAC operation schedules were determined using an analysis involving a simplified HVAC model, which was calibrated against daily data measured by the LoanSTAR program. It is estimated that annual savings of 67,000, or 13% of the annual costs, can be realized using the optimized operation schedules which can be implemented without additional costs. Our analysis indicates that the room comfort levels will not be degraded by these measures
A Prediction of Energy Savings Resulting from Building Infiltration Control
Heat transfer through building walls
consists of three main components:
conduction heat transfer, solar gain and
infiltration heat transfer. An interaction
among these three heat transfer
components alters the effective heat
transfer through a wall, working to
reduce or increase it. This study uses
simulation to evaluate the potential
energy impact of the interaction when
several different strategies for
controlling air leakage direction and
velocity in building envelope
components are implemented.
The simulations performed in this study
show that significant energy savings can
be realized with the use of controlled
airflow through non-airtight walls in a
building. Comparing the energy load of
a building which uses airflow control in
its walls with the energy load found
with a standard calculation (where the
interaction effect is not considered),
annual energy load savings were found
in a warm climate as high as 17%. The
results were less promising when
compared against the performance of a
building experiencing simulated natural
airflow (and heat recovery) through its
exterior walls: the best annual load
savings percentage was 10% in a warm
climate. It was found that in a cooler
climate, the natural flow configuration
performed about as well as any of the
artificial airflow configurations, so airflow control is not recommended in
cool climates
A Report on the Environmental Impact of the Texas LoanSTAR Program from May 1989 to September 1995
There are a number of factors that influence emission factors. The three major pollutants considered in this analysis are CO2, SO2, and NOX. Emission factors from three different sources were considered for this report. This analysis shows that as of September, 1995, there has been a reduction in emissions of 1.88 million pounds of NOX, 1.19 million pounds of SO2, and 532 million pounds of CO2 through the implementation of energy conservation measures in the Texas LoanSTAR program.The Texas LoanSTAR (Loans to Save Taxes and Resources) program was created by the state of Texas in 1989 to lend money for energy conserving improvements, or retrofits, in public buildings. As of September 1995 the LoanSTAR program is measuring savings for 22 loan sites covering 153 buildings where retrofits have been fully or partially completed. The completed retrofits show $21.1 million in measured savings, which is more than 119% of the energy savings predicted by the energy auditors. This corresponds to 23.9% of the pre-retrofit consumption cost at these sites. Through energy savings, the Texas LoanSTAR program has made a significant contribution towards reducing hazardous environmental emissions
Rehabilitating A Thermal Storage System Through Commissioning
A thermal storage system was installed in a
37,000 ft2 hospital in April 1992. The chiller
had to be operated every summer during peak
demand periods until the authors rehabilitated
system through building commissioning in late
1995. This paper presents information about the
building systems, commissioning activities, and
the measured energy savings which resulted
from the process
Signatures of Heating and Cooling Energy Consumption for Typical AHUs
An analysis is performed to investigate the
signatures of different parameters on the heating
and cooling energy consumption of typical air
handling units (AHUs). The results are presented
in graphic format. HVAC simulation engineers
can use these graphs to make quick and rational
decisions during the model calibration, identify
faulty parameters, and develop optimized
operation and control schedules. An application
example is given as well in the paper
- …